型号 | FY400-302000 | 加工定制 | 否 |
---|---|---|---|
测量精度 | 1000 | 结构型式 | 嵌入式 |
显示方式 | 液晶显示 | 外形尺寸 | 48*48mm |
开孔尺寸 | 42*42mm | ||
OFF K
2 Temperature unit
ON °F
OFF °C
3 NC
4 Input type selection for the third
input (Input 2)
ON Analog input
OFF Thermocouple
5 Input type selection for the fourth
input (Input 3)
ON Analog input
OFF Thermocouple
6 Analog input signal range
ON 1 to 5V/4 to 20mA
OFF 0 to 10V
Temperature input
Input type Range (°C) Range (°F)
K -200.0 to 1300.0 -300 to 2300
J -100.0 to 850.0 -100.0 to 1500
pecifications
*1 Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max.
*2 Accuracy for a K-type sensor at -100°C or less is ±10°C ±1 digit max.
DIP Switch Settings
The DIP switch is used to set the temperature unit and to set the temperature input range.
Note: Set the temperature range according to the type of temperature sensor connected to the Unit. Temperature data will not be converted correctly if the temperature
range does not match the sensor.
■CP1W-SRT21 CompoBus/S I/O Link Unit
The CompoBus/S I/O Link Unit functions as a slave for a CompoBus/S Master Unit (or an SRM1 CompoBus/S Master Control Unit) to form an I/O
Link with 8 inputs and 8 outputs between the CompoBus/S I/O Link Unit and the Master Unit.
Item CP1W-TS004
Temperature sensors Thermocouples
Switchable between K and J, but same type must be used for all inputs.
Number of inputs 12
Accuracy
25°C (The larger of ±0.5% of converted value or </span>±2°C) ±1 digit max. *1
0 to 55°C (The larger of ±1% of converted value or </span>±4°C) ±1 digit max. *2
Conversion time 500 ms for 12 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
2-decimal-place mode is not supported
Isolation Photocouplers between any two input signals
Current consumption 5 VDC: 80 mA max., 24 VDC: 50 mA max.